|
| |
 |
The
10 Commandments of Cooling systems |
|
- Maintain Proper Cycles of
Concentration and Saturation Indices.
- Maintain Proper Treatment (Inhibitor
& Biocide).
- Keep Feed & Control Equipment Set
Properly, Operating and Calibrated.
- Passivate. Keep Distribution
Decks Covered. Maintain Equal Water Distribution.
- Know Make-Up Water Characteristics.
Make Proper Product Selections.
- Know Operating Characteristics of
Equipment (Chillers, AHU & Towers).
- Keep Tower Basin Clean.
Maintain Proper Water Level.
- Record Equipment operating
Temperature/Pressures and Pump & Controller Settings.
- Report Scaling/Corrosive Conditions.
Review Daily Logs - Evaluate Trends.
- Have full knowledge of communication
with, and, training of, operating, supervisory and management
personnel.
|
|
|
 |
Automating
biocide feed to cooling systems |
|
Microbiological control can
be frustrating at times. One of the most important elements in a
biocide program is to apply the product in the correct dosage at specific
intervals. The concept of not adding biocide until you see an
indication of "algae" places you in the position of playing
"catch up" on microbiological control. The interval at
which a biocide should be applied is based on your system's specific retention
time.
Retention time is
calculated based on system volume and bleed off rate. When biocide
is added to a system, the recommended dose is based on your system water
volume. This dose establishes a specific level of the biocide's
active ingredient. Through the normal cycling and subsequent bleed
off of the system, the level of biocide is gradually lowered to a point
where the biocide can become ineffective. The time frame from one
biocide addition until the next is important. If the level of
biocide is allowed to fall below its effective range, microbiocidal
proliferation can occur.
Much of today's system
control equipment incorporates automatic biocide features and many
existing controllers can have this retrofitted. This can also be
accomplished by adding a timing device and chemical metering pump to your
existing control equipment. The timer can then be set to add the
correct dose of biocide at the intervals dictated by the calculated
retention time.
Automatic biocide feeding
will establish a consistent, effective biocide treatment program and free
up the man-hours used to manually apply the biocide. An added
benefit of automation is that it will reduce handling of the microbiocide
product as well as reduce the change of waste from spills and measuring
errors.
If you think you may be
interested in automating your biocide treatment program, discuss the
options and benefits that are available with your Water Treatment
Consultant.
|
|
|
 |
cleaning
cooling towers |
|
Cooling Towers
should be cleaned periodically to remove dirt, mud, and debris from the
basin. These items can form a barrier between the metal of the basin
and the water. When the inhibitors are not in contact with the
basin, under deposit corrosion can occur. Under deposit corrosion is
just as it sounds, corrosion occurring under a deposit. It should
also be noted that mud, dirt, and debris in the cooling tower basin
provide an excellent breeding ground for microbiological organisms.
Some microorganisms secrete an acidic solution that can increase
corrosion.
At least once
a year, Cooling Tower evaporative salts need to be cleaned. This is
done differently on each tower as different fill material requires
different cleaning procedures. The distribution decks and
distribution nozzles should be checked and cleaned or replaced as needed
at the same time.
If the
tower can be shut down, drained, flushed, and pressure washed, this would
be the preferred method of cleaning. As the tower is being refilled,
it is important that the proper Water Treatment inhibitor level is added
to ensure adequate system protection upon system start up. If the
tower cannot be shut down, do not despair. You can do a fairly good
job of cleaning a cooling tower while it is on-line with a vacuum or
siphon arrangement; that will allow you to remove the bulk of mud and
debris that accumulate in the tower basin's low flow areas. A
disadvantage to cleaning on-line is that there will be some debris that
will become dislodged and will end up being re-circulated in the bulk
water and will settle out in the basin in a day or so. However, this
is the preferred method of Tower Cleaning throughout the year when debris
is in the Tower Basin. Again, after the cleaning, make sure the
inhibitor level is brought back into the normal control range.
|
 |
the
dilemma of tower overflow in "bleed & feed programs" |
|
A common problem that the
Water Treater encounters in "bleed and feed" cooling treatment
is tower overflow. Although this is a common problem, the harm that
is does to the chemical treatment is not generally well understood by the
customer and may not be corrected immediately.
In a "bleed and
feed" regimen, a system controller uses a probe in a constant flow of
water to maintain a certain "safe" dissolved solid level to
prevent scale formation on heat transfer surfaces. When the probe
senses the maximum solid level established by the controller setting, it
electronically activates a bleed valve which begins purging concentrated
water from the system. At the same time, a chemical metering pump is
also activated which begins pumping scale and corrosion inhibitor into the
system. The pump is set to add a certain amount of inhibitor
necessary to control scale and corrosion based upon the amount of bleed
required to maintain the desired solids level.
When a tower overflows, it
is because the make-up valve is either not adjusted properly to maintain a
"low-enough" water level in the tower, or it is no longer
functional and needs replacement. When overflow occurs, the properly
treated water is lost from the system and the make-up valve is constantly
adding fresh water to the system thereby causing a dilution. This
dilution is not called for by the controller, so no inhibitor is added.
If evaporation is great enough after the overflow has happened, the system
will "cycle up" again without the necessary inhibitor level, and
scale will form. Not only does overflow undermine the "bleed
and feed" cycle, it creates a state of poor water usage adding to the
customer's water and sewage costs. When tower overflow is found, the
make-up valve should be properly adjusted or replaced immediately.
Once the correct tower water level is achieved, the proper inhibitor
levels should be restored by manually adding treatment to the tower so
that a sound bleed and feed program can continue.
|
 |
Tower
freeze protection |
|
Through the cooler months
we have noticed different freeze protection techniques. The most
common of these is overflowing. The following will point out some of
the problems associated with this practice.
While overflowing the tower
addresses freezing of condenser and make-up water, it also creates a few
problems. Overflowing causes conductivity to drop. If the
tower has a feed/bleed controller, once the system is returned to normal,
the inhibitor level will be low. It must be brought back into range
to prevent the build-up of scale and to control corrosion. If your
system has a proportional feed system, while you overflow water, you also
waste chemical. With this in mind, you may ask yourself, "How
do I properly protect my system from freezing?"
Water only freezes at 32°
F or less, and this can be extended much below that if the system is
recirculating. Most chiller manufacturers recommend you do not start
your system if your condenser water is below 65° F. As a result,
many towers have basin water heaters and/or tower by-passes. If the
forecast indicates freezing weather, turn on the basin heaters and
circulate the water or by-pass the tower. If the make-up line needs
protection, heat stripping or insulation is recommended. These
actions will eliminate the need to readjust the make-up float as the
weather changes.
Many preventative
maintenance programs recommend overflowing, but, as already pointed out,
this may cause more problems than you anticipate. If you have any
specific questions or concerns regarding your system, please discuss them
with your Water Treatment Consultant.
|
 |
water
common sense |
|
Cooling Systems
Often times Water Treatment
Consultants have problem situations arise that are easily avoided with a
little applied common sense. Some customers feel that instead of
figuring out a problem on their own, will wait until their Consultant's
service visit and let them address it. This unfortunately only
causes further problems. Maintenance and engineering staffs have a
great advantage over the Water Treatment Consultant. They are at
their facility daily and can observe changes in the system, which allows
them to prevent any great problems from arising. The Water Treatment
Consultant is only in a facility once or twice a month typically.
Listed below are a few
basic procedures that should always be performed on a regular basis.
For a relatively small amount of time, these actions can save time and
money.
First, test the system and
chemical levels. This will greatly eliminate problems down the road
because once an oddity arises you can address it immediately and prevent
scale and corrosion from occurring.
In cooling towers, a common
problem can be low or high conductivity level even though the controller
calibrated. Three reasons are often the cause:
-
A failed solenoid due
to no signal or power to the solenoid.
-
Trash keeping the
solenoid either open or closed.
-
Excessive water level
in the basin. Often in the cooler months when the demand on the
tower is less, the system comes on line periodically and often the
tower overflows when the recirculation pump shuts off.
Uncontrolled water loss causes the tower to refill when on line with
untreated water and can cause scale and corrosion problems.
Low or high chemical levels
are also a problem that occasionally occurs. If so, check and see if
one of these might be the reason:
If the level is low:
-
Has the pump lost
prime?
-
Is the pump getting the
signal to energize?
If the level is high:
-
Is the bleed valve
bleeding when called for?
For high levels the most
obvious solution is to turn down the pump (make sure to check levels
regularly to ensure that the adjustment wasn't too much. Adjusting
chemical levels and dosages is not like turning on a light switch and
getting immediate results, it is necessary to check later to make sure the
correct changes were made.
After testing is complete
and chemical additions are made, if everything is all right, pay yourself
on the back. If there are any problems, spend some time trying to
solve them.
|
 |
solids
accumulation in water systems due to evaporation |
|
|
Example:
|
A 50-ton tower
system
1,000 gallons total water capacity
Evaporates 90 gph Delta T = 10º
|
|
|
|
This
water contains .05 lbs. solids per gallon.
|
|
Initially,
|
1,000 gallons x .05 = 50 lbs. solids
|
|
|
|
|
1 hour later:
|
910 gallons,
with 50 lbs. solids
|
|
|
90 gallons
makeup x .05 = 4.5 lbs. solids
|
|
|
1,000 gallons
with 54.5 lbs. solids
|
|
|
|
|
After 2 hours:
|
910 gallons,
with 54.5 lbs. solids
|
|
|
90 gallons
makeup, with 4.5 lbs. solids
|
|
|
1,000 gallons,
with 59 lbs. solids
|
|
|
|
|
After 3
hours:
|
910 gallons with
59 lbs. solids
|
|
|
90 gallons
makeup with 4.5 lbs. solids
|
|
|
1,000 gallons
with 63.5 lbs. solids
|
|
|
|
|
After 12
hours:
|
1,000 gallons
with 104 lbs. solids
|
|
|
|
|
After 24
hours:
|
1,000 gallons
with 158 lbs. solids
|
The solids level has
tripled in just 24 hours!!
|
|